ClareOne - Installation Sheets
  1. Help Center
  2. ClareOne Essentials
  3. ClareOne - Installation Sheets

ClareOne Rate of Rise Heat Detector Installation Sheet

CLR-C-HT

Image 001

Description

The ClareOne Rate-Of-Rise heat detector uses a built-in thermistor to sample and report on a specific set temperature or a sudden rise in temperature.

Heat – selectable 135F or 200F

Rate of Rise – rapid temp rise 12F per minute

Note: The device is powered by a 3V lithium battery providing up to 10 years of battery life.

Installation

Heat detectors are normally installed in areas that are prone to smoke such as kitchens and garages.

Installation notes:

  • Avoid areas that may have rapidly increasing temperatures such as fireplaces, stoves, heaters, etc.
  • When mounting the detector should be placed on a ceiling at least 4 inches away from any wall. If placed on a wall the detector must be within 6 inches of the ceiling.
  • If using the sensor with the heat setting at 135°F make sure the ceiling location does not exceed this temperature.

Setup:

The detector can be setup to detect a fixed temperature of either 135F or 200F.

Low – 135F

High – 200F

Note: if no jumper is installed the detector is set to 200F

To set detection temperature: Use the jumper to select Low or Hi.
Image 002

Programming

To add the sensor to your panel and for detailed programming instructions, refer to the ClareOne Wireless Security and Smart Home Panel User Manual (DOC ID 1871).

To add the detector:

  1. Put the ClareOne panel in “add mode” and follow the displayed instructions for adding the sensor.
  2. Open the sensor body case and depress the tamper switch.
  3. Exit “add mode.”

    Image 003

Mounting the detector

  1. Locate the base mounting holes and mount the base to the wall or ceiling with the appropriate hardware.
  2. Attach the detector to the mounting base.

    Image 004

Replacing the batteries

Battery life depends on the temperature of the installation environment. When the battery voltage gets low, the detector transmits a low battery signal to the panel. The panel then activates trouble beeps to notify the customer that the detector battery must be replaced.

Replace the battery immediately when this condition occurs, using the following battery: Panasonic CR123A 3V

Battery disposal

The batteries used in this sensor are lithium batteries and are not reusable. Be sure to properly dispose of used lithium batteries according to your local hazardous waste disposal laws.

 

Specifications

Compatible panel

ClareOne (CLR-C1-PNL1)

Transmitter frequency

433MHz

Encrypted

Yes

Transmitted indications

Tamper and low batter

Supervisory keep-alive

60 to 70 minutes

Maximum UL spacing

50 x 50 ft (15.2 x 15.2 m)

Rate of rise rating

12 to 15°F (6.7 to 8.3°C)

UL max ambient ceiling

100 to 150°F (37.8 to 65.6°C)

Battery type

CR123A

Battery life

8 to 10 years

Temperature detection

135º F rate of rise

Heat rate of rise detection

15º F per minute

Operating environment                Temperature               
Relative humidity


32 to 150°F (0 to 65.6°C)
0 to 95% noncondensing

Dimensions

2.29 × 1.28 in.
(58.25 × 32.4 mm)

Certifications

FCC: 15.109 Class B 15.231, Industry Canada: ICES-003, RSS-210

 

Full PDF - ClareOne Rate-of-Rise Heat Detector Installation Sheet (DOC ID 1945)